Section 3
REF615 standard configurations
3.4.3.4
90
functions are blocked by the master trips TRPPTRC1_86/94-1 and TRPPTRC2_86/94-2
and the circuit breaker open signal.
It is assumed that there is no external resistor in the circuit breaker tripping
coil circuit connected in parallel with the circuit breaker normally open
auxiliary contact.
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR1_TCM-1_ALARM
TCSSCBR2_TCM-2_ALARM
GUID-2A1FB8E2-51CC-461D-B04D-8A2893C8F381 V1 EN
Figure 81:
Trip circuit supervision function
TRPPTRC1_86/94-1_TRIP
TRPPTRC2_86/94-2_TRIP
X120_BI3_CB_OPEN
GUID-A43E0483-878F-4B65-A336-0794F43E61CC V1 EN
Figure 82:
Logic for blocking of trip circuit supervision

Functional diagrams for control and interlocking

The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input
can be activated using the configuration logic, which is based on the status of the trip
logics. However, other signals can be connected based on the application needs.
The SYNC_ITL_BYP input can be used, for example, to always enable the closing of the
circuit breaker when the circuit breaker truck is in the test position. SYNC_ITL_BYP
overrides, for example, active interlocking conditions when the circuit breaker truck is
closed in service position.
TCSSCBR1
BLOCK
ALARM
O:113|T:5|I:1
TCSSCBR2
BLOCK
ALARM
O:114|T:5|I:2
OR
B1
O
B2
O:115|T:2.5|I:16
OR6
B1
O
B2
B3
B4
B5
B6
O:112|T:2.5|I:35
1MAC109016-MB C
TCSSCBR1_TCM-1_ALARM
TCSSCBR2_TCM-2_ALARM
TCSSCBR_ALARM
TCSSCBR_BLOCKING
REF615 ANSI
Application Manual