Section 3
REF615 standard configurations
3.3
3.3.1
3.3.2
42

Standard configuration D

Applications

The standard configuration for non-directional overcurrent and non-directional ground-
fault protection is mainly intended for cable and overhead-line feeder applications in
directly or resistance grounded distribution networks.
The protection relay with a standard configuration is delivered from the factory with
default settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the protection relay enables this configuration to be
further adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

Functions

52
3
GUID-D0C1421A-5B6D-4FD1-A187-1ADC8D5B061D V1 EN
Figure 14:
Functionality overview for standard configuration D
REF615 V5.0 FP-1 ANSI Func Appl D
51P-1
50P-1
50P-2
50P-3
3
49F-1
46PD
46-2
Load
50
INR-1
Prof.
BF-1
51N-1
51G
50G-1
50G-3
HIZ-1
AFD-
AFD-
AFD-
79
2
3
3
3
1
2
3
1
Available with Harmonic-based earth-fault option
2
Available with Reclosing option
3
Available with Arc Flash Detection(AFD) option
4
Available with RTD option
1MAC109016-MB C
46-1
50N
BF-1
1
51NHA
38
4
Application Manual
REF615 ANSI