Section 4
Requirements for measurement transformers
200
A071142-ANSI V2 EN
Figure 254:
Example of three-stage overcurrent protection
The maximum three-phase fault current is 41.7 kA and the minimum three-phase short
circuit current is 22.8 kA. The actual accuracy limit factor of the CT is calculated to be 59.
The pickup current setting for low-set stage (51P) is selected to be about twice the nominal
current of the cable. The trip time is selected so that it is selective with the next protection
relay (not visible in
Figure
stage are defined also so that grading is ensured with the downstream protection. In
addition, the pickup current settings have to be defined so that the protection relay
operates with the minimum fault current and it does not trip with the maximum load
current. The settings for all three stages are as in
For the application point of view, the suitable setting for instantaneous stage (50P-3) in
this example is 3 500 A (5.83 × I
of the CT. For the CT characteristics point of view, the criteria given by the current
transformer selection formula is fulfilled and also the protection relay setting is
considerably below the F
selected much lower than 10 VA for economical reasons.
254). The settings for the high-set stage and instantaneous
Figure
). I
is the 1.2 multiple with nominal primary current
2n
2n
. In this application, the CT rated burden could have been
a
1MAC109016-MB C
254.
REF615 ANSI
Application Manual