Section 3
REF615 standard configurations
52
ARCSARC1_AFD-1_TRIP
ARCSARC2_AFD-2_TRIP
ARCSARC3_AFD-3_TRIP
GUID-C6165736-DE76-486B-97A3-E92CA54D3B15 V1 EN
Figure 23:
Arc protection
The optional autoreclosing function is configured to be initiated by trip signals from a
number of protection stages through the INIT_1...5 inputs. It is possible to create
individual autorecloseing sequences for each input.
The autoreclosing function can be inhibited with the INHIBIT_RECL input. By default,
few selected protection function operations are connected to this input. A control
command to the circuit breaker, either local or remote, also blocks the autoreclosing
function via the CBXCBR1_52-1_SELECTED signal.
The circuit breaker availability for the autoreclosing sequence is expressed with the
CB_READY input in DARREC1_79. This signal is not connected in the configuration.
The open command from the autorecloser is connected directly to binary output
X100:PO3, whereas the close command is connected directly to binary output X100:PO1.
Set the parameters for DARREC1_79 properly.
ARCSARC1
BLOCK
TRIP
REM_FLT_ARC
ARC_FLT_DET
OPR_MODE
O:18|T:2.5|I:11
ARCSARC2
BLOCK
TRIP
REM_FLT_ARC
ARC_FLT_DET
OPR_MODE
O:17|T:2.5|I:21
ARCSARC3
BLOCK
TRIP
REM_FLT_ARC
ARC_FLT_DET
OPR_MODE
O:19|T:2.5|I:31
OR6
B1
O
B2
B3
B4
B5
B6
O:92|T:2.5|I:30
1MAC109016-MB C
ARCSARC1_AFD-1_TRIP
ARCSARC1_AFD-1_ARC_FLT_DET
ARCSARC2_AFD-2_TRIP
ARCSARC2_AFD-2_ARC_FLT_DET
ARCSARC3_AFD-3_TRIP
ARCSARC3_AFD-3_ARC_FLT_DET
ARCSARC_TRIP
REF615 ANSI
Application Manual