ABB RELION 615 Series Applications Manual page 184

Feeder protection and control relay
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
178
SEQRFUF2_60-2_FUSEF_U
SEQRFUF2_60-2_FUSEF_U
SEQRFUF2_60-2_FUSEF_U
GUID-9DE7CD91-E7CF-4259-8444-F319579843BC V1 EN
Figure 233:
Voltage functions on bus 2
The circuit-breaker failure protection CCBRBRF_50BF is initiated via the PICKUP input
by a functions connected to the Master Trip 1 and by opening command of the circuit
breaker. CCBRBRF_50BF offers different operating modes associated with the circuit-
breaker position and the measured phase and residual currents.
CCBRBRF_50BF has two operating outputs: TRRET and TRBU. The TRBU output can be
used to give a backup trip to the circuit breaker feeding upstream. In the configuration the
TRBU output signal is connected to the output SO1 (X100: 14, 15, 16).
CCBRBRF1_50BF-1 use the source 1 (bus 1) voltages whereas CCBRBRF2_50BF-2 use
the source 2 (bus 2) voltages.
PHPTUV2
BLOCK
TRIP
PICKUP
O:78|T:5|I:2
PHPTOV2
BLOCK
TRIP
PICKUP
O:75|T:5|I:2
NSPTOV2
BLOCK
TRIP
PICKUP
O:76|T:5|I:2
ROVPTOV3
BLOCK
TRIP
PICKUP
O:73|T:5|I:3
1MAC109016-MB C
PHPTUV2_27-2_TRIP
PHPTOV2_59-2_TRIP
NSPTOV2_47-2_TRIP
ROVPTOV3_59N-2_TRIP
REF615 ANSI
Application Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion ref615 ansi

Table of Contents