1MAC109016-MB C
3.6.3.1
REF615 ANSI
Application Manual
Functional diagrams for protection
The functional diagrams describe the relay's protection functionality in detail and
according to the factory set default connections.
Four overcurrent stages are offered for overcurrent and short-circuit protection. Three of
them include directional functionality DPHxPDOC_67/5xP. Three-phase non-directional
overcurrent protection, instantaneous stage, PHIPTOC1_50P-3 can be blocked by
energizing the binary input X120: BI1.
X120_BI1_EXT_OC_BLOCKING
DPHHPDOC1_67/50P-1_TRIP
DPHLPDOC1_67/51P-1_TRIP
DPHLPDOC2_67/51P-2_TRIP
DPHHPDOC2_67/50P-2_TRIP
GUID-8293227D-FAB7-4E29-B3CF-52277091C321 V1 EN
Figure 168:
Overcurrent protection functions
REF615 standard configurations
PHIPTOC1
BLOCK
TRIP
ENA_MULT
PICKUP
O:22|T:2.5|I:1
DPHHPDOC1
BLOCK
TRIP
ENA_MULT
PICKUP
NON_DIR
O:24|T:5|I:1
DPHHPDOC2
BLOCK
TRIP
ENA_MULT
PICKUP
NON_DIR
O:14|T:5|I:2
DPHLPDOC1
BLOCK
TRIP
ENA_MULT
PICKUP
NON_DIR
O:25|T:5|I:1
DPHLPDOC2
BLOCK
TRIP
ENA_MULT
PICKUP
NON_DIR
O:50|T:5|I:2
OR6
B1
O
B2
B3
B4
B5
B6
O:117|T:2.5|I:61
Section 3
PHIPTOC1_50P-3_TRIP
PHIPTOC1_50P-3_PICKUP
DPHHPDOC1_67/50P-1_TRIP
DPHHPDOC1_67/50P-1_PICKUP
DPHHPDOC2_67/50P-2_TRIP
DPHHPDOC2_67/50P-2_PICKUP
DPHLPDOC1_67/51P-1_TRIP
DPHLPDOC1_67/51P-1_PICKUP
DPHLPDOC2_67/51P-2_TRIP
DPHLPDOC2_67/51P-2_PICKUP
DPHxPDOC_TRIP
139