ABB RELION 615 Series Applications Manual page 193

Feeder protection and control relay
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MAC109016-MB C
TRPPTRC1_86_94-1_TRIP
TRPPTRC2_86_94-2_TRIP
GUID-ACF312FD-FAE1-4AF9-9727-EA5701905F3D V1 EN
Figure 244:
Circuit breaker control
REF615 ANSI
Application Manual
CB1_POSITION_OPEN
CB1_POSITION_CLOSE
NOT
IN
OUT
O:113|T:2.5|I:2
CB2_POSITION_OPEN
CB2_POSITION_CLOSE
NOT
IN
OUT
O:43|T:2.5|I:3
If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker
control function block CBXCBR_52 with PCM600, the function assumes that the breaker
close commands are allowed continuously.
The sync check function SECRSYN1_25 is provided in this standard configuration. The
main purpose of the synchronism and energizing check is to provide control over the
closing of the circuit breakers in power networks to prevent the closing if the conditions
for synchronism are not detected. The energizing function allows closing, for example,
when one side of the breaker is dead.
The sync check function measures the bus and line voltages and compares them to set
conditions. When all the measured quantities are within set limits, the output SYNC_OK is
activated for allowing closing of the circuit breaker. The SYNC_OK output signal of
SECRSYN1_25 is connected to ENA_CLOSE input of CBXCBR1_52-1.
By default, Bus 1 is designated as the bus side and Bus 2 as the line side. Thus, LLDB
means that Bus 2 is live and Bus 1 is dead; similarly, LLLB means that both Bus 2 and 1
REF615 standard configurations
CBXCBR1
POSOPEN
SELECTED
POSCLOSE
EXE_OP
ENA_OPEN
EXE_CL
ENA_CLOSE
OP_REQ
BLK_OPEN
CL_REQ
BLK_CLOSE
OPENPOS
AU_OPEN
CLOSEPOS
AU_CLOSE
OKPOS
TRIP
OPEN_ENAD
SYNC_OK
CLOSE_ENAD
SYNC_ITL_BYP
O:69|T:5|I:1
CBXCBR2
POSOPEN
SELECTED
POSCLOSE
EXE_OP
ENA_OPEN
EXE_CL
ENA_CLOSE
OP_REQ
BLK_OPEN
CL_REQ
BLK_CLOSE
OPENPOS
AU_OPEN
CLOSEPOS
AU_CLOSE
OKPOS
TRIP
OPEN_ENAD
SYNC_OK
CLOSE_ENAD
SYNC_ITL_BYP
O:46|T:5|I:2
Control
CTRL_OFF
OFF
CTRL_LOC
LOCAL
CTRL_STA
STATION
CTRL_REM
REMOTE
CTRL_ALL
ALL
BEH_TEST
BEH_BLK
O:4|T:2.5|I:0
Section 3
CBXCBR1_52-1_EXE_OP
CBXCBR1_52-1_EXE_CL
CBXCBR2_52-2_EXE_OP
CBXCBR2_52-2_EXE_CL
187