REF615 ANSI
Application Manual
CB1_POSITION_CLOSE
CB2_POSITION_CLOSE
GUID-0F178891-90AB-4A90-8E4F-53ACCEA7A9F0 V1 EN
Figure 242:
Fuse failure monitoring
Note that BUS1_Voltage_Presence and BUS2_Voltage_Presence reflect Bus 1 and 2
voltage status respectively. Depending on the application, these signals can be built on the
status of all the breakers that are connected to voltage sources. Take the Main-Tie-Tie-
Main application as an example and consider a rotating machine on the buses.
GUID-2CC2E9D5-B0B4-409D-A907-08A6F818175D V1 EN
Figure 243:
Main-Tie-Tie-Main system
To properly determine the voltage presence on a bus, the positions of all the breakers that
are connected to the bus must be known. For example, consider the Bus 1 in the above
diagram, the incomer source 1, MT1 and other voltage through the tie breakers are
REF615 standard configurations
SEQSPVC1
BLOCK
FUSEF_3PH
CB_CLOSED
FUSEF_V
DISCON_OPEN
MINCB_OPEN
O:14|T:2.5|I:1
SEQSPVC2
BLOCK
FUSEF_3PH
CB_CLOSED
FUSEF_V
DISCON_OPEN
MINCB_OPEN
O:66|T:2.5|I:2
Section 3
SEQRFUF1_60-1_FUSEF_U
SEQRFUF2_60-2_FUSEF_U
185