ABB RELION 615 Series Applications Manual page 107

Feeder protection and control relay
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MAC109016-MB C
REF615 ANSI
Application Manual
Analog input
Description
VA
Phase voltage VA
VB
Phase voltage VB
VC
Phase voltage VC
Table 22:
Default connections for binary inputs
Binary input
Description
X110-BI1
-
X110-BI2
-
X110-BI3
Circuit breaker open position indication
X110-BI4
Circuit breaker closed position indication
X110-BI5
-
X110-BI6
-
X110-BI7
-
X110-BI8
-
Table 23:
Default connections for binary outputs
Binary output
Description
X100-PO1
Close circuit breaker
X100-PO2
Circuit breaker failure protection trip to upstream breaker
X100-SO1
General pickup indication
X100-SO2
General trip indication
X100-PO3
Open circuit breaker/trip coil 1
X100-PO4
Open circuit breaker/trip coil 2
X110-SO1
Upstream overcurrent blocking
X110-SO2
Overcurrent trip alarm
X110-SO3
Ground-fault trip alarm
X110-SO4
Voltage protection trip alarm
X110-HSO1
Arc protection instance 1 trip activated
X110-HSO1
Arc protection instance 2 trip activated
X110-HSO1
Arc protection instance 3 trip activated
REF615 standard configurations
Connector pins
X131:7-8
X132:7-8
X133:7-8
Connector pins
BIO0005
X110:1-2
X110:3-4
X110:5-6
X110:7-6
X110:8-9
X110:10-9
X110:11-12
X110:13-12
Connector pins
X100:6-7
X100:8-9
X100:10-11,(12)
X100:13-14
X100:15-19
X100:20-24
X110:14-16
X110:17-19
X110:20-22
X110:23-24
X110:15-16
X110:19-20
X110:23-24
Section 3
BIO0007
X110:1,5
X110:2,5
X110:3,5
X110:4-5
X110:6,10
X110:7,10
X110:8,10
X110:9-10
101