ABB RELION 615 Series Applications Manual page 64

Feeder protection and control relay
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
SSCBR1_52CM-1_TRV_T_OP_ALM
SSCBR1_52CM-1_TRV_T_CL_ALM
SSCBR1_52CM-1_SPR_CHR_ALM
SSCBR1_52CM-1_OPR_ALM
SSCBR1_52CM-1_OPR_LO
SSCBR1_52CM-1_IPOW_ALM
SSCBR1_52CM-1_IPOW_LO
SSCBR1_52CM-1_CB_LIFE_ALM
SSCBR1_52CM-1_MON_ALM
SSCBR1_52CM-1_PRES_ALM
SSCBR1_52CM-1_PRES_LO
GUID-79BF3B58-B0F3-490A-96CB-52031D35EB2C V1 EN
Figure 31:
Logic for circuit breaker monitoring alarm
58
X120_BI3_CB_OPEN
X120_BI2_CB_CLOSED
CB_OPEN_COMMAND
CB_CLOSE_COMMAND
GUID-0B65542D-6DE7-4B60-B79A-BE23D184A8C0 V1 EN
Figure 30:
Circuit-breaker condition monitoring function
OR6
B1
B2
B3
B4
B5
B6
O:60|T:2.5|I:15
OR6
B1
B2
B3
B4
B5
B6
O:61|T:2.5|I:14
Two separate trip circuit supervision functions are included: TCSSCBR1_TCM-1 for
power output X100:PO3 and TCSSCBR2_TCM-2 for power output X100:PO4. Both the
functions are blocked by the master trip TRPPTRC1_86/94-1 and TRPPTRC2_86/94-2
and the circuit breaker open signal.
It is assumed that there is no external resistor in the circuit breaker tripping
coil circuit connected in parallel with the circuit breaker normally open
auxiliary contact.
SSCBR1
BLOCK
TRV_T_OP_ALM
POSOPEN
TRV_T_CL_ALM
POSCLOSE
SPR_CHR_ALM
OPEN_CB_EXE
OPR_ALM
CLOSE_CB_EXE
OPR_LO
PRES_ALM_IN
IPOW_ALM
PRES_LO_IN
IPOW_LO
SPR_CHR_ST
CB_LIFE_ALM
SPR_CHR
MON_ALM
RST_IPOW
PRES_ALM
RST_CB_WEAR
PRES_LO
RST_TRV_T
OPENPOS
RST_SPR_T
INVALIDPOS
CLOSEPOS
O:59|T:5|I:1
O
OR
B1
B2
O:62|T:2.5|I:11
O
1MAC109016-MB C
SSCBR1_52CM-1_TRV_T_OP_ALM
SSCBR1_52CM-1_TRV_T_CL_ALM
SSCBR1_52CM-1_SPR_CHR_ALM
SSCBR1_52CM-1_OPR_ALM
SSCBR1_52CM-1_OPR_LO
SSCBR1_52CM-1_IPOW_ALM
SSCBR1_52CM-1_IPOW_LO
SSCBR1_52CM-1_CB_LIFE_ALM
SSCBR1_52CM-1_MON_ALM
SSCBR1_52CM-1_PRES_ALM
SSCBR1_52CM-1_PRES_LO
O
SSCBR1_52CM-1_ALARMS
REF615 ANSI
Application Manual