1MAC109016-MB C
REF615 ANSI
Application Manual
Table 17:
Default connections for binary outputs
Binary output
Description
X100-PO1
Close circuit breaker
X100-PO2
Circuit breaker failure protection trip to upstream breaker
X100-SO1
General pickup indication
X100-SO2
General trip indication
X100-PO3
Open circuit breaker/trip coil 1
X100-PO4
Open circuit breaker/trip coil 2
X110-SO1
Upstream overcurrent blocking
X110-SO2
Overcurrent trip alarm
X110-SO3
Ground-fault trip alarm
X110-SO4
Voltage protection trip alarm
X110-HSO1
Arc protection instance 1 trip activated
X110-HSO1
Arc protection instance 2 trip activated
X110-HSO1
Arc protection instance 3 trip activated
Table 18:
Default connections for LEDs
LED
Default usage
1
Overcurrent protection trip
2
Ground-fault protection trip
3
Voltage protection trip
4
Negative sequence overcurrent
or phase discontinuity
protection trip
5
Thermal overload alarm
6
Circuit breaker failure
protection backup protection
trip
7
Disturbance recorder triggered
8
Circuit breaker condition
monitoring alarm
9
Supervision alarm
10
Arc flash detection
11
Autoreclose in progress
REF615 standard configurations
ID
LED_Overcurrent_1
LED_EarthFault_1
LED_OverUnderVoltage_1
LED_PhaseUnbalance_1
LED_ThermalOverload_1
LED_BreakerFailure_1
LED_DisturbRecTriggered_1
LED_CBConditionMonitoring_
1
LED_Supervision_1
LED_ArcDetected_1
LED_AutorecloseInProgress_1
Section 3
Connector pins
X100:6-7
X100:8-9
X100:10-11,(12)
X100:13-14
X100:15-19
X100:20-24
X110:14-16
X110:17-19
X110:20-22
X110:23-24
X110:15-16
X110:19-20
X110:23-24
Label description
Overcurrent
Ground-fault
Over/under voltage
Phase unbalance
Thermal overload
Breaker failure
Disturb. rec. triggered
CB condition monitoring
Supervision
Arc detected
Autoreclose shot in progr.