Rs-## Resolver Interface - GE AF-650 GP Programming Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions

3.15 RS-## Resolver Interface

RS-50 Poles
Range:
2
[2 - 8] Set the number of poles on the resolver.
*
3
3
The value is stated in the data sheet for resolvers.
RS-51 Input Voltage
Range:
7 V
[2 - 8 V] Set the input voltage to the resolver. The
*
RS-52 Input Frequency
Range:
10 kHz
[2 - 15 kHz] Set the input frequency to the resolver.
*
RS-53 Transformation Ratio
Range:
0.5
[0.1 - 1.1] Set the transformation ratio for the resolver.
*
RS-59 Resolver Interface
Activate the OPCRES resolver option when the resolver
parameters are selected.
To avoid damage to resolvers RS-50 Poles – RS-53 Transformation
Ratio must be adjusted before activating this parameter.
Option:
[0]
*
[1]
3.16 Parameter Data Check
3.16.1 Last 10 Changes
Displays a list of the 10 last changes made to the
parameters in the present parameter setup. This allows for
any corrections of the last 10 changes.
3.16.2 Since Factory Settings
Displays a list of all the parameter changes since the
factory settings of the drive or since the last factory restore
of parameters.
108
Function:
Function:
voltage is stated as RMS value.
The value is stated in the data sheet for
resolvers
Function:
The value is stated in the data sheet for
resolvers.
Function:
The transformation ration is:
V Out
T ratio
=
V In
The value is stated in the data sheet for
resolvers.
Function:
Disabled
Enabled
AF-650 GP Programming Guide
3.17 ID-## Drive Information
Parameter group related to drive information such as
operating data, hardware configuration and software
version.
3.17.1 ID-0# Operating Data
Parameters to view operating hours. kWh counters, power
ups, etc.
ID-00 Operating hours
Range:
0 h
[0 - 2147483647 h] View how many hours the frequency
*
ID-01 Running Hours
Range:
0 h
[0 - 2147483647
*
h]
ID-02 kWh Counter
Range:
0 kWh
*
ID-03 Power Up's
Range:
0
[0 - 2147483647] View the number of times the frequency
*
ID-04 Over Temp's
Range:
0
[0 - 65535] View the number of frequency converter
*
ID-05 Over Volt's
Range:
0
[0 - 65535] View the number of frequency converter
*
ID-06 Reset kWh Counter
Option:
[0]
Do not reset
*
[1]
Reset counter Press [OK] to reset the kWh counter to zero
DET-618C
Function:
converter has run. The value is saved
when the frequency converter is
turned off.
Function:
View how many hours the motor has
run. Reset the counter in ID-07 Reset
Running Hours Counter. The value is
saved when the frequency converter is
turned off.
Function:
[0 - 2147483647
Registering the power consumption
kWh]
of the motor as a mean value over
one hour. Reset the counter in
ID-06 Reset kWh Counter.
Function:
converter has been powered up.
Function:
temperature faults which have occurred.
Function:
overvoltages which have occurred.
Function:
Nno reset of the kWh counter is desired.
(see ID-02 kWh Counter).

Hide quick links:

Advertisement

Table of Contents
loading