Starting The Drive Remotely; Starting The Drive Locally - ABB ACS6000 User Manual

System drives
Hide thumbs Also See for ACS6000:
Table of Contents

Advertisement

• If the drive is equipped with a DC link disconnector, check that the
control switch for the DC link disconnector is in the
correct position.
8.9.2

Starting the drive remotely

When the drive system is operated from a higher-level control system or
an operator control desk, follow the instructions in the
applicable manuals.
8.9.3

Starting the drive locally

1. Set the CDP control panel to local control mode.
1.
2. If the EMERGENCY-OFF RESET push button on the COU is flashing,
press the push button to cancel flashing.
Note: Each time the auxiliary voltage is switched off and on again, the
emergency-off safety relay of the drive is actuated and lets the
EMERGENCY-OFF RESET pushbutton flash. The EMERGENCY-OFF
RESET push button also flashes if the EMERGENCY-OFF push button
on the control compartment door, or any other EMERGENCY-OFF push
button linked to the drive, is pressed. If the EMERGENCY-OFF RESET
push button continuous flashing, verify that there is no emergency-off
command active. See "8.10.2 Stopping the drive with the emergency-
off function" on page 195
3. Check that no alarm or fault messages are displayed on the
control panel.
• When a fault message is displayed on the control panel, reset
the fault.
• If a fault cannot be reset, the responsible personnel must rectify it.
• (Drives with an ARU) When faults are present and the drive is ready,
the INU is "ReadyOn".
3BHS212794 E01 REV M
1 L ->
4840.0 V
StateARU
ReadyOn
DC VOLT
0.00 V
PRI VOLT
0 V
ACS6000 USER MANUAL
08 OPERATION
190/278