Lamp Does Not Light Up; Lamp Lights Up - ABB ACS6000 User Manual

System drives
Hide thumbs Also See for ACS6000:
Table of Contents

Advertisement

• Lamp does not light up:

- Lamp is burnt out
- Lamp-test circuit is faulty.
The lamp-test circuit and the grounding circuit are independent of
each other. From the lamp not lighting up, it cannot be concluded
that the discharging circuit and / or the grounding circuit are
not working.

• Lamp lights up:

- discharging circuit and / or the grounding circuit
are malfunctioning.
3. Verify that the MCB (main circuit breaker) is open.
• If the MCB is open, secure it against closing.
• Check if the LED of digital input DI14 (input module A2531 in COU1)
is lit.
• If the LED is lit, the feedback signal "MCB is open" is present.
4. Verify that hazardous voltages from the motor cannot be fed into
the drive.
5. Check if the LED of digital output DO07 (output module A2541 in
COU1) is lit.
• If the LED is lit, the grounding switch is released.
6. Check the discharging level of the DC link.
• If the value of the parameter 2.01 DC VOLTAGE is below 50 V, the DC
link is discharged.
• If the DC link is discharged, the drive is in "ReadyOn" status.
• Check that the message ReadyOn is displayed on all control panels
of the drive.
7. Carefully turn the grounding switch to the grounded position on the
following conditions:
• Hazardous voltages cannot be fed into the drive from the main
power supply or the motor
• DC link is discharged
• Grounding switch is released (DO07 is energized)
• Drive status is "ReadyOn"
3BHS212794 E01 REV M
10 PREVENTIVE AND CORRECTIVE MAINTENANCE
1 L ->
0.0 rpm 0
StateINU
ReadyOn
MOTOR SP
0.00 rpm
POWER
0.0 kW
ACS6000 USER MANUAL
235/278

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents