Cable Entry Systems; Frames With Type 1 Sealing Modules; Cable Entry With Type 1 Sealing Modules - ABB ACS6000 User Manual

System drives
Hide thumbs Also See for ACS6000:
Table of Contents

Advertisement

4. Wind up the excess cable lengths to the reeling device in the REB.
NOTICE These cables are only available in standard lengths and cannot
be cut or extended. The excess cable must be wound up in coils with a
diameter of at least 100 mm.
6.5

Cable entry systems

Depending on your drive configuration, one or a combination of the
following cable entry systems might be used on a cabinet for top and/or
bottom cable entry:
• "6.5.1 Frames with type 1 sealing modules" on page 135
• "6.5.2 Frame with type 2 sealing modules" on page 137
• "6.5.3 Plates with cable glands" on page 137
• "6.5.4 EMC plates with sealing grommets" on page 138
Note: For information on the location and the dimensions of the cable
entry, see "Appendix C – Mechanical drawings".
6.5.1

Frames with type 1 sealing modules

1
(1) Compression wedge
(2) Sealing module (RM120)
Usage
Included in delivery
Not included in
delivery
3BHS212794 E01 REV M
Figure 6-9 Cable entry with type 1 sealing modules
• Power cables
• Ground cables
• Equipotential bonding conductors
• Cable entry frame
• Sealing modules
• Accessories
• Tools
ACS6000 USER MANUAL
06 ELECTRICAL INSTALLATION
(3) Cable entry frame
2
3
135/278