• Optional fieldbus adapters for serial data transfer to a higher-level
control system
• DriveWare® software tools:• includes software tools such as the
commissioning and maintenance tools DriveWindow and
DriveDebug, and DriveOPC for data transfer between ABB drives
and Windows®-based applications.
• NETA-21: monitoring and diagnostics tool that allows access to the
drive from any location in the world via a secure
Internet connection.
3.2.5.7

Local control panels

Each control unit (COU) is equipped with a local control panel. The control
panel serves as the basic user interface for monitoring, control and
operation of the drive and setting of parameters.
Figure 3-16 Local control panels on 1000 mm COU (A) and 600 mm COU (B)
Note: For more information, see:
• "8 Operation" on page 173
• "9 CDP control panel" on page 199
3.2.5.8

S800 I/O system

Standard S800 I/O modules connect the internal and external I/O signals
to the control system. External I/O signals connect to the terminals inside
the water cooling unit (WCU) and are wired internally to their I/O modules.
An S800 I/O station consists of up to 12 I/O modules and a TB 820 bus
modem that serves as an interface to the AMC circuit boards. Each I/O
module is plugged into a module termination unit that contains the S800
I/O module bus. The module bus transmits the data between the bus
modem and the I/O modules. The number of S800 I/O stations per drive
depends on the drive configuration.