8.10.4

Starting the drive system after an emergency-off

1. To start the drive system after an emergency-off, unlatch the
EMERGENCY-OFF push button.
The EMERGENCY-OFF push button returns to its initial position when
turned into the direction indicated by the arrows on the push button.
2. Press the EMERGENCY-OFF RESET button to reset the emergency-off
safety relay of the drive.
• The drive remains in emergency-off state until the DC-link voltage
has dropped to < 50 V (discharged).
• After resetting, the status message of the drive changes
to "ReadyOn".
The status line of the CDP control panel shows the following:
1 L ->
StateINU
MOTOR SP
POWER
3. The main power supply can be connected to the drive again and the
drive system can be started up.
3BHS212794 E01 REV M
0.0 rpm
EmergencyOff
0.00 rpm
0.0 kW
ACS6000 USER MANUAL
Alternating display message:
• EmergencyOff
• EOFF<DCVolt
08 OPERATION