Aru Cable Entry Frames With Type 1 Sealing Modules; Removing The Short Busbars; Short Busbar Removal In Aru - ABB ACS6000 User Manual

System drives
Hide thumbs Also See for ACS6000:
Table of Contents

Advertisement

6.6.2

ARU cable entry frames with type 1 sealing modules

Depending on the configuration of the drive, ARUs can be equipped with
3 cable entry frames (size 3) on the cabinet floor.
In order to connect the cables, you need to remove the phase modules (see
"10.4.10 Removing and installing a phase module" on page 253) and, if
necessary, the short busbars as well ("6.6.2.0.1 Removing the short
busbars" on page 140).

6.6.2.0.1 Removing the short busbars

1. Remove the phase module according to "10.4.10 Removing and
installing a phase module" on page 253.
2. If necessary, remove the short busbars (boxes) to facilitate entering
the cables.
3. To remove a busbar, unscrew the bottom bracket and the bolts and
then move the busbar downward and away from the cabinet.
(1) Short busbar
(2) Remove these bolts
(3) Bottom bracket
4. After you have routed the cables, install the busbars in the reverse
order of removal.
3BHS212794 E01 REV M
1
2
1
2
Figure 6-15 Short busbar removal in ARU
ACS6000 USER MANUAL
06 ELECTRICAL INSTALLATION
1
1
3
(4) 1/2" wrench
(5) 17 mm and 19 mm
4
5
140/278