Description, device design, dimension drawing
2.4 Operating displays and signaling
Legend:
LED off
LED lights up
0.5/3
LED flashes in the interval: 0.5 s on - 3 s off
LED 1 (O.K./BAT)
Signaling
Off
Red
Flashing red (0.5/0.5)
Flashing red (1/1)
Flashing yellow
(0.5/0.5)
Flashing yellow (0.5/3)
Yellow
Flashing green (0.5/3)
Green
LED 2 (BAT>85 %)
Signaling
Flashing green
(0.5/0.5)
Off
Green
LED 3 (alarm)
Signaling
Red
Off
28
6EP4134-3AB00- ...
6EP4136-3AB00- ...
6EP4137-3AB00- ...
DC-UPS off
DC-UPS defect (severe hardware fault)
Firmware update
Software corrupted
Critical temperature reached, overtemperature or overvoltage at the input.
Buffer mode, output off
Buffer mode, output on
DC-UPS OK, output off
DC-UPS OK, output on
6EP4134-3AB00- ...
6EP4136-3AB00- ...
6EP4137-3AB00- ...
Firmware update
Battery charge state <85 %
Battery charge state >85 %
6EP4134-3AB00- ...
6EP4136-3AB00- ...
6EP4137-3AB00- ...
Output off for 45 seconds because of overcurrent, overtemperature or buffer operation not
possible
Buffer operation possible
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76