Firmware Update - Siemens SITOP UPS1600 Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

3.5.12

Firmware update

The SITOP UPS1600 is reset while updating the firmware. For safety reasons, the output is
switched off.
Ensure that no damage is caused to the plant or system.
Ensure that the PG/PC and/or all switches, routers and gateways that are used have an
independent power supply during the firmware update.
Note
Do not switch-off the devices during the firmware update.
The files for updating the firmware (firmware updates) are available online under
(http://support.automation.siemens.com/WW/view/en/79207181). Different firmware updates
are offered depending on the amp rating of the SITOP UPS1600.
Note
Observe the compatibility of the firmware!
Other firmware updates are not compatible.
Determine the amp rating of your SITOP UPS1600 and download the appropriate firmware
update.
Note
It is not possible to downgrade the device firmware to a release with a version number lower
than the firmware installed in the device itself. Information on how to read out the firmware
release from the device is provided in Section Display and visualization (Page 106).
Note
"Reset to factory" function:
Everything is reset, also the IP address. A new IP address must then be assigned, as
otherwise there is no connection to the UPS Manager or TIA.
Preconditions
● The SITOP UPS1600 has been correctly connected and linked with the system.
● PG/PC with SITOP UPS Manager is connected with the system.
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
WARNING
Engineering and remote access
3.5 SITOP UPS Manager
111