3.5.8.2

Configuring the SITOP UPS1600

Using the SITOP UPS Manager, you can configure the SITOP UPS1600 and its energy
storage device, and then load to the device (if it is an uncoded battery - for UPS1100, the
values are automatically identified). To change the charge parameters switch-in threshold or
buffer time, you must set the corresponding rotary coding switch to the "REN" position.
1. To do this, select "Hardware configuration > Base device" or "Hardware configuration
> Energy storage".
2. Enter the desired values.
3. Click on "Download"
Configuring the basic device (base unit)
The following parameters are available under "Hardware configuration> Base unit".
Parameter
Location
Connection threshold
Buffer time
Maximum buffer time
1)
Additional buffer time after PC shutdown
Expected buffer current
1)
Reset time
Enable reset time after buffering:
Downtime alarm
Wait time for stable input voltage
Variable time for battery test
Parameter only available from V2.0.0 and higher
1)
Parameter only available from V2.1 and higher
2)
● Location: Details of the location identification where the SITOP UPS1600 is installed.
● Connection threshold: If the connection threshold value is fallen below, the
SITOP UPS1600 starts buffering. If the value of the connection threshold is reached or
undershot again later, the SITOP UPS1600 stops buffering.
● Buffer time: Length of time during which the system should be buffered by the
SITOP UPS1600.
● Maximum buffer time: The MAX setting means that buffering is realized for as long as
possible. The device only shuts down when the battery has discharged down to the
defined stop buffering voltage. The value entered for the "Buffer time" parameter is not
relevant in this case.
● Additional buffer time after PC shutdown: The time in which the system is buffered by the
SITOP UPS1600 once the PC has been shut down.
● Expected buffer current: Load current, which is expected at the device output during
buffer operation. If a value of 0 A is entered, then for this parameter, the average value of
the actual load current measured at the output over the last 10 min is assumed. The
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
2)
Value range
Free text
21 - 25 V
1 - 32767 s
Yes / No
1 - 300 s
0 - 40 A
1 - 120 s
Yes / No
0 - 20000 ms
0.2 - 65 s
1 - 65535 h
Engineering and remote access
3.5 SITOP UPS Manager
Default setting
22.5 V
60 s
No
10 s
0 A
5 s
No
125 ms
0.5 s
4 h
101