Maintenance; Battery; Battery Replacement - Siemens SITOP UPS1600 Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

7.7

Maintenance

7.7.1

Battery

SITOP UPS1100 devices contain 2 maintenance-free batteries.
Device type
6EP4131-0GB00-0AY0 (1.2 Ah)
6EP4132-0GB00-0AY0 (2.5 Ah)
6EP4133-0GB00-0AY0 (3.2 Ah)
6EP4133-0JB00-0AY0 (5 Ah)
6EP4134-0GB00-0AY0 (7 Ah)
6EP4135-0GB00-0AY0 (12 Ah)
When replacing the batteries, always use batteries with the same batch number
(approximately the same charge state).
The rechargeable batteries must be disposed of, discharged according to the applicable
regulations.
When storing, installing and operating the buffer batteries, the regulations of VDE 0510 Part
2 / EN 50272-2 or the applicable national regulations must be observed.
The self-discharge rate of the batteries is approx. 3%/month for a temperature of 20° C. This
value is temperature dependent and becomes more unfavorable for an increasing
temperature, and more favorable for a decreasing temperature.
7.7.2

Battery replacement

See Image 7-5 Maintenance (Page 154) and Image 7-6 Wiring schematic (Page 154)
1. Remove the screws
2. Open the cover.
3. Press button
LED
4. Remove fuse
5. Replace the batteries.
6. Press the button for at least 2 s
LED
7. Insert the fuse.
8. Close the cover (screw).
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
using a Torx T10 screwdriver.
for at least 2 s.
flashes
stops flashing and lights continuously.
Battery type
YUASA NP1,2-12
Hawker Energy CYCLON 0810-0075 2.5-12
YUASA NP3,2-12 or B.B.Battery BP3,6-12
NEC ALM12V7s
YUASA NP7-12 or B.B.Battery BP7-12
YUASA NP12-12 or B.B.Battery BP12-12
Installation
7.7 Maintenance
153