Mounting position, mounting clearances
6.1
SITOP UPS1600
6.1.1
Standard mounting position
The device is designed for mounting on standard EN 60715 35×7.5/15 mounting rails. The
device must be mounted vertically to ensure proper cooling, and with the input terminals and
output terminals at the bottom.
A clearance of at least 50 mm should be maintained above and below the device.
No clearance is required at the side.
Output current as a function of the ambient temperature
Image 6-1
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
6EP4134-3AB00-... : Output current in the standard mounting position
6
145