Data Sets - Siemens SITOP UPS1600 Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Engineering and remote access
3.7 Cyclic and acyclic data
Index
Slot
Subslot Data set
0x0007 0
1
0x0008 0
1
0x0009 0
1
0x0020 0
1
0x0040 0
1
0x0041 0
1
You can find detailed information about the individual data sets in Section Data sets
(Page 124)
3.7.2.1

Data sets

In this section you can find detailed information about the individual data sets that are sent
from the PROFINET IO-Controller to the SITOP UPS1600 - and which can be read from the
SITOP UPS1600.
0x0001: Buffering parameters (reading/writing)
Data
Buffer time [1 s]
Buffer time 2 [1 s]
Buffer threshold [0.01 V]
Stop buffering voltage [0.01 V]
Input voltage OK time [1 ms]
124
Type
Hardware settings
Reading
parameters
Buffering parameters
Reading /
from V2.0
writing
Maintenance parame-
Reading /
ters from V2.1
writing
State information
Reading
Identification value
Reading /
parameters
writing
Web server
Reading /
parameters
writing
Description
Buffer time: After the selected buffer time has expired, the
SITOP UPS1600 switches off the load output. The actual buffer
time that can be achieved depends on the connected loads and
energy storage devices.
Additional buffer time after PC shutdown. The specified value is 5
seconds (only valid in conjunction with the PC software
SITOP UPS Manager)
Connection threshold: Switching voltage for buffering. Buffering is
active below this value.
Stop buffering voltage: Buffer operation is exited if the battery
voltage is below this value.
Wait time for stable input voltage: Minimum time during which the
input voltage during buffer operation must be available at the
SITOP UPS1600 to exit buffer operation of the SITOP UPS1600
and to again supply the connected loads via the input voltage
(normal operation).
Description
Hardware settings of the
SITOP UPS1600 (settings that were
made at the front of the device).
Buffer parameters of the
SITOP UPS1600
Maintenance parameters of
SITOP UPS1600
Status information about
SITOP UPS1600 and the connected
battery modules SITOP UPS1100.
Information about the SITOP UPS1100
battery modules is available via the link
"Energy Storage".
Device identification parameters.
Web server settings of the
SITOP UPS1600.
Manual, 04.2016, A5E37775406-6-76
Data size
8 bytes
2 bytes
2 bytes
64 bytes
70 bytes
(from V2.1)
80 bytes
108 bytes
(from V2.1)
1 byte
6 bytes (from
V2.1)
Data type
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
SITOP UPS1600 / UPS1100