● Maximum buffer time
The setting means that buffering is realized for as long as possible. The device only shuts
down when the battery has discharged down to the defined stop buffering voltage. The
value entered for the "Buffer time" parameter is not relevant in this case.
● Additional buffer time after PC shutdown
Time during which the system should be buffered by the SITOP UPS1600 after the PC
was shut down.
● Expected buffer current
Load current, which is expected at the device output during buffer operation. If a value of
0 A is entered, then for this parameter, the average value of the actual load current
measured at the output over the last 10 min is assumed. The value of this parameter is
used when calculating the remaining buffer time. The entered value may not exceed the
rated device current.
● Stop buffering voltage
The voltage at which battery discharge is terminated. The stop buffering voltage defined
for this type is always used for a coded battery (UPS1100).
● Enable reset
If the value is set to "Yes" then the output voltage is interrupted after the selected buffer
time expires if, in the meantime, the input voltage returns. This option is useful, when, for
example, computer networks are protected by the UPS that can be activated by a reset
when the power supply is restored. For buffer time "MAX", the output voltage is not
interrupted.
● Reset time
Here, you define the interrupt duration.
"Signaling" parameter
Parameter
Downtime alarm
Wait time for stable input voltage
● Downtime alarm
The time in which no alarm is issued to the system although it is buffered.
● Wait time for a stable input voltage
Time where the input voltage must continually lie above the connection threshold so that
buffering is exited and a transition is made into normal operation.
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
3.3 SIMATIC STEP 7 in the TIA Portal
Value range
0 - 20,000 ms
0.2 - 65 s
Engineering and remote access
Default setting
125 ms
0.5 s