Siemens SITOP UPS1600 Manual page 130

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Engineering and remote access
3.7 Cyclic and acyclic data
0x0007: Hardware setting parameters (reading)
Data
Buffer time [1 s]
Buffer threshold [0.01 V]
Buffering allowed
Enable reset
Start from battery
Selected battery profile
0x0008: Buffering parameters (reading/writing)
Data
Expected buffer current [0.1 Ah]
from V2.0 and higher
0x0009: Maintenance parameters (reading/writing)
Data
Resistor test interval [1 h] from
V2.1
0x0020: State information (reading)
Data
Remaining buffer time [1 s]
Total operating time [1 h]
Total calculated battery capacity
[0.1 Ah]
Calculated battery 1 capacity
[0.1 Ah]
Calculated battery 2 capacity
[0.1 Ah]
130
Description
Buffer time: After the selected buffer time has expired, the
SITOP UPS1600 switches off the load output. The actual buffer
time that can be achieved depends on the connected loads and
energy storage devices.
Connection threshold: Switching voltage for buffering. Buffering is
active below this value.
Activate or deactivate buffer operation. The setting is only accept-
ed in operating mode Remote Enable (REN) of the
SITOP UPS1600.
Enable reset: If, during buffer operation, the input voltage be-
comes available again, then the output of the SITOP UPS1600 is
switched off for a selectable time in order to reset connected
loads.
Start from battery: Setting at the signal terminal for function "Start
from battery".
Profile of the selected battery: The battery charging behavior is set
at the signal terminals. The setting is only used, if the
SITOP UPS1600 is not in the "Remote Enable" (REN) mode
Description
Expected buffer current: Estimated average load current during
buffer operation.
Description
R test interval
Description
Probable remaining buffer time. The remaining buffer time is cal-
culated based on the present battery charge and the average
current over a 10 minute period.
Total operating time.
Total calculated battery capacity
Battery 1: Calculated battery capacity.
Battery 2: Calculated battery capacity.
Data type
Unsigned16
Unsigned16
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Data type
Unsigned16
Data type
Unsigned16
Data type
Unsigned32
Unsigned32
Unsigned16
Unsigned16
Unsigned16
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76