Procedure
The firmware update consists of several files, which are combined in a zip file.
1. Download the firmware update.
2. Unpack the ZIP file into a temporary directory.
3. In the network view, select the components whose firmware is to be updated.
4. Change to the device view.
5. Click on "Go online".
6. In the shortcut menu of the SITOP UPS1600, select "Online & Diagnostics".
The "Online access" menu opens.
7. In the "Functions" folder, select the "Firmware update" group.
8. Click on the "Browse" button in the "Firmware loader" area to select the path to the
directory with the unzipped files.
9. Select file "ups10a.upd", "ups20a.upd", "ups40a.upd". All SITOP UPS1600 are displayed
in the table, for which an update is possible with the selected firmware file.
10.Click on the "Start update" button. If the selected file can be interpreted by the module, it
will be loaded into the module. For version V2.1 - depending on the UPS1600 type - the
firmware file is called "ups20a.upd", for example. If this requires changing the operating
state of the CPU, you will be prompted to do this with dialogs.
11.Confirm the notes that are displayed.
The firmware is sent from the controller to the component . While sending, LED 4 ("SF")
and LED 6 ("RUN") flash at the SITOP UPS1600.
12.Confirm the message from the TIA Portal that the data was successfully sent by pressing
"OK".
The firmware is saved in the internal component memory. The following LEDs flash while
saving:
– LED 1 ("OK/Bat")
– LED 2 (">85%")
Note
It can take several minutes to save the firmware in the component. Do not switch-off the
devices.
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
Engineering and remote access
3.3 SIMATIC STEP 7 in the TIA Portal
63