Engineering and remote access
3.3 SIMATIC STEP 7 in the TIA Portal
Proceed as follows
1. Open the "Online > Accessible nodes" menu.
2. As type of PG/PC interface, select "PN/IE".
3. Select the PG/PC interface connected with the system.
4. Select the connection with the subnet, in which the SITOP UPS1600 is located.
All of the available SITOP UPS1600 devices in the selected subnet are displayed.
5. Select the required SITOP UPS1600.
6. Activate the "Flash LED" checkbox.
7. Check at which SITOP UPS1600 in the network the "SF" LED flashes.
By checking the flashing LEDs, you can uniquely identify all SITOP UPS1600 in a network.
Note the device name and the IP address of the required SITOP UPS1600 in order to load a
configuration.
Changing the device name of the SITOP UPS1600
1. In STEP 7 , in the tabular area of the Network view, select the "Network overview" table.
2. Overwrite the name in the "Device" column in the row of the PROFINET device involved.
You have changed the name of the SITOP UPS1600 device.
The name is adapted in the graphical area of the network view.
Changing the PROFINET device name of the SITOP UPS1600 via the properties of the PROFINET
interface
You can change the PROFINET device name using the properties of the PROFINET
interface.
1. In the Network or Device of view of the hardware and network editor from STEP 7, select
the PROFINET interface of a PROFINET device.
2. In the Inspector window navigate to "Ethernet addresses" in the "PROFINET" area.
3. Deactivate the "Generate automatically the PROFINET device name" checkbox.
4. Enter the new PROFINET device name in the appropriate field.
56
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76