7.2
Connecting the SITOP UPS1600 at its output
The output of the SITOP UPS1600 is no-load, overload and short-circuit proof. If an overload
occurs, the electronic current limiting function limits the output current to a maximum value
(see Section Technical data (Page 155)).
Image 7-3
The output voltage is connected at the "OUT+" and "OUT–"
Output-side connection (Page 151)). Ensure that the output cables are dimensioned
correctly for the maximum output current rms value and fused accordingly.
The deployed cables must be suitable for temperatures of at least 90° C. (only for
applications for UL508)
7.3
Connecting the BAT SITOP UPS1600
Image 7-4
The "BAT+" and "BAT-"
used to connect the SITOP UPS1600 with one or more SITOP UPS1100 battery modules.
Ensure that the cables are dimensioned correctly for the maximum output current rms value
of the SITOP UPS1600.
For wiring, see Image 7-1 Wiring (Page 150).
Cables must be used that are suitable for at least 90 °C (only for applications for UL508).
Maximum cable length 3 m
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
Output-side connection
BAT connection
③
connections (see Image 7-4 BAT connection (Page 151)) are
7.2 Connecting the SITOP UPS1600 at its output
②
terminals (see Image 7-3
Installation
151