Engineering and remote access
3.5 SITOP UPS Manager
5. To check whether the application will performed correctly, click the "Start" button.
6. Enter the time in minutes and seconds after which the application should be started.
Note
Only those applications that do not open any Windows screen can be started.
Behavior during buffer mode
Make the settings under "Software configuration > Buffer operation" vor.
The following options are available:
● Start application on power failure.
● Start application after power return.
● Show SITOP UPS Manager on power failure.
● Show SITOP UPS Manager after power return.
● Shut down PC on power failure after xx minutes.
Note
NOTICE: If the buffer time (see Section Configuring the SITOP UPS1600 (Page 101)) is set
shorter than this time, the SITOP UPS1600 switches off before the PC has been shut down.
The PC is then no longer protected.
Behavior for missing buffer readiness
Make the settings under "Software configuration > Not ready for buffering".
The following options are available:
● Start the application if buffer mode is not possible.
● Start the application when buffer readiness returns
● Open the SITOP UPS Manager if buffer mode is not possible
● Open the SITOP UPS Manager when buffer readiness returns.
Behavior when battery replacement required
Make the settings under "Software configuration > Battery replacement".
The following options are available:
● Start the application if battery replacement is recommended (from SITOP UPS Manager
V4.12.5 and higher).
● Start the application once the battery has been replaced.
104
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76