Siemens SITOP UPS1600 Manual page 127

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Data
Batt 12 Maximal temperature [1 °C] Highest specified operating temperature of the battery module
Fill byte(s)
Batt 2: Order number
Batt 2: Serial number
Batt 2: Manufacturing date
Batt 2: Version number
Batt 3: Standby time [1 s]
Batt 3: Buffer time [1 s]
Batt 3: Total charging current
[1 mA]
Batt 3: Total culled current [1 mAh]
Batt 3: EOCV [0.01 V]
Batt 3: Charge current [1 mA]
Batt 3: Battery capacity [0.1 Ah]
Batt 3: Stop buffering voltage
[0.01 V]
Batt 3: Battery type
Batt 3: Minimal temperature [1 °C]
Batt 3: Maximal temperature [1 °C]
Fill byte(s)
Batt 3: Order number
Batt 3 Serial number
Batt 3: Manufacturing date
Batt 3: Version number
Batt 4: Standby time [1 s]
Batt 4: Buffer time [1 s]
Batt 4: Total charging current
[1 mA]
Batt 4: Total culled current [1 mAh]
Batt 4: EOCV [0.01 V]
Batt 4: Charge current [1 mA]
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
Description
being used SITOP UPS1100.
-
Order number (Article number).
Serial number
Manufacturing date
Version number
Standby time.
Required buffer time, after which the SITOP UPS1600 shuts down
in the buffer mode.
Total charge current (battery-specific data): Total charge within the
service lifetime of the SITOP UPS1600.
Total charge level used (battery-specific data): Time, in which the
battery is connected to the SITOP UPS1600 and power was
drawn.
"End-of-charge voltage": Battery voltage when charging changes
to trickle charging. The energy storage device is then charged up
to 100 %.
Charge current: Current magnitude used to charge the connected
battery modules during the constant charging process.
Battery capacity: Total battery capacity of all energy storage de-
vices connected to the SITOP UPS1600.
Stop buffering voltage: Buffer operation is exited if the battery
voltage is below this value.
Battery type
Lowest specified operating temperature of the battery module
being used SITOP UPS1100.
Highest specified operating temperature of the battery module
being used SITOP UPS1100.
-
Order number (Article number).
Serial number
Manufacturing date
Version number
Standby time.
Required buffer time, after which the SITOP UPS1600 shuts down
in the buffer mode.
Total charge current (battery-specific data): Total charge within the
service lifetime of the SITOP UPS1600.
Total charge level used (battery-specific data): Time, in which the
battery is connected to the SITOP UPS1600 and power was
drawn.
"End-of-charge voltage": Battery voltage when charging changes
to trickle charging. The energy storage device is then charged up
to 100 %.
Charge current: Current magnitude used to charge the connected
battery modules during the constant charging process.
Engineering and remote access
3.7 Cyclic and acyclic data
Data type
Signed8
3xUnsigned8
VisibleString(30)
VisibleString(30)
VisibleString(30)
VisibleString(50)
Unsigned32
Unsigned32
Unsigned32
Unsigned32
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned8
Signed8
Signed8
3xUnsigned8
VisibleString(30)
VisibleString(30)
VisibleString(30)
VisibleString(50)
Unsigned32
Unsigned32
Unsigned32
Unsigned32
Unsigned16
Unsigned16
127