Data
Downtime alarm [1 ms]
Buffering allowed
Enable reset after buffering
0x0002: Battery parameters (reading/writing)
Data
Battery defect voltage [0.01 V]
Battery capacity [0.1 Ah]
Ignore battery coding
0x0003: Charging parameters (reading/writing)
Data
End of charge voltage [0.01 V]
Charge current [1 mA]
0x0004: Reset parameters (reading/writing)
Data
Reset time [1 s]
0x0005: Battery information parameters (reading)
Data
Number of batteries
Fill byte(s)
Batt 1: Standby time [1 s]
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
Description
Downtime alarm: Alarm filter - alarm is only sent if it is active for
longer than the set time.
Activate or deactivate buffer operation. The setting is only accept-
ed in operating mode Remote Enable (REN) of the
SITOP UPS1600.
Enable reset after buffering: If, during buffer operation, the input
voltage becomes available again, then the output is switched off
for a selectable time in order to reset the connected devices.
Description
Battery defect voltage: If the battery voltage falls below the set
value, then the battery is identified to be defective.
Battery capacity: Total battery capacity of all energy storage de-
vices connected to the SITOP UPS1600.
Ignore data of the coded battery: When this parameter is set to
"1", then data of the coded battery is ignored. Instead, data is
taken from the parameterization ("Battery Parameters", "Charging
Parameters").
Description
End of charge voltage: Battery voltage when charging changes to
trickle charging. The connected energy storage device is then
charged up to 100 %.
Charge current: Current magnitude used to charge the connected
battery modules during the constant charging process.
Description
Reset time: Time during which the SITOP UPS1600 output is
shutdown if the connected devices are reset.
Description
Number of connected battery modules. Here, only the
SITOP UPS1100 battery modules (coded batteries) are counted.
-
Standby time.
Engineering and remote access
3.7 Cyclic and acyclic data
Data type
Unsigned16
Unsigned8
Unsigned8
Data type
Unsigned16
Unsigned16
Unsigned8
Data type
Unsigned16
Unsigned16
Data type
Unsigned8
Data type
Unsigned8
3xUnsigned8
Unsigned32
125