1. In the Network or Device view of the hardware and network editor from STEP 7 in the TIA
Portal , select PROFINET interface of a PROFINET device.
2. In the Inspector window navigate to "Ethernet addresses" in the "IP protocol" area.
3. Check whether the "Set IP address in the project" option is activated.
4. Enter the new IP address in the appropriate field.
Loading the configuration to the SITOP UPS1600
To commission the UPS, you must load the project data that you created offline into the
connected SITOP UPS1600. This project data results from the configuration of the hardware,
networks and connections in STEP 7.
Initially, the complete project data is loaded. Only the changes are loaded for subsequent
load actions.
Preconditions
● The project data is consistent.
● The device name must be identical offline and online.
● The SITOP UPS1600 is accessible online.
● The SITOP UPS1600 is located in the PROFINET IO system of an IO controller.
● The PG/PC is connected to the same network to which the SITOP UPS1600 and the
controller are connected. The interface of the PG/PC must be set to TCP/IP.
Note
Ensure that the article number of the SITOP UPS1600 configured offline matches the article
number of the device connected online. The following response is obtained after loading the
configuration into the device:
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
Engineering and remote access
3.3 SIMATIC STEP 7 in the TIA Portal