Description, device design, dimension drawing

2.3 Operator controls

2.3
Operator controls
2.3.1

SITOP UPS1600

2.3.1.1

Rotary coding switch, switch-in threshold

The switch-in threshold can be set using the rotary coding switch
between 21.0 V and 25.0 V (21 - 21.5 - 22 - 22.5 - 23 - 24 - 25 volt). The delivery state is
22.5 V
For devices with an interface (...-1AY0, ...-2AY0), the coding switch has an additional REN
position. If this is selected, the software settings (for the switch-in threshold and the backup
time) apply rather than the hardware settings. In the switch position REN, the connection
X2.13 (INTERRUPT - reset after buffer operation) of the signal terminal (see Section Signal
terminal (Page 18)) has no effect.
Image 2-11
Note
It is only permissible to operate the rotary switch using an insulated screwdriver.
For notes on actuating the rotary coding switch (screwdriver, torque), see Image 2-3
Terminal data SITOP UPS1600 10 A, 20 A (Page 17).
2.3.1.2

Rotary coding switch, backup time

The buffer time is set using the rotary coding switch
seconds and MAX in steps of 0.5 minute (30 s), 1 minute, 2 minutes, 5 minutes, 10 minutes,
20 minutes and MAX. The MAX setting means that buffering is realized for as long as
possible. The device only shuts down when the battery has discharged down to the stop
buffering voltage (factory setting, 18.5 V). Delivery state is MAX.
The rotary coding switch has an additional setting OFF (see following diagram). If this is
selected and the additional threshold rotary coding switch is not set to REN, then buffering is
deactivated.
If the buffer time is to be set using the software (only for devices with an interface (...-1AY0,
...-2AY0)) (possible setting range, see Section Parameterizing SITOP UPS1600 (Page 70)),
the rotary coding switch for the connection threshold (see Section Rotary coding switch,
switch-in threshold (Page 22)) must be set to REN.
22
Rotary coding switch, switch-in threshold
on the device front
on the device front between 30
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76