Fault
F30003: DC link voltage, un-
dervoltage
Message class: Infeed faulted
(13)
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F30004: Drive heat sink over-
temperature
Message class: Power electron-
ics faulted (5)
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F30005: Power unit: Overload
I
t
2
Message class: Power electron-
ics faulted (5)
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F30011: Line phase failure in
main circuit
Message class: Network fault
(2)
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F30015: Phase failure motor
cable
Message class: Applica-
tion/technological function faulty
(17)
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F30021: Ground fault
Message class: Ground
fault/inter-phase short-circuit
detected (7)
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2020, A5E37208830-008
Cause
The power unit has detected an un-
dervoltage condition in the DC link.
Line supply failure
Line supply voltage below the per-
missible value.
Line supply infeed failed or interrupt-
ed.
Line phase interrupted.
The temperature of the power unit heat
sink has exceeded the permissible limit
value.
Insufficient cooling, fan failure.
Overload.
Surrounding temperature too high.
Pulse frequency too high.
The power unit was overloaded.
The permissible rated power unit
current was exceeded for an inad-
missibly long time.
The permissible load duty cycle was
not maintained.
At the power unit, the DC link voltage
ripple has exceeded the permissible limit
value.
Possible causes:
A line phase has failed.
The 3 line phases are inadmissibly
unsymmetrical.
The fuse of a phase of a main circuit
has ruptured.
A motor phase has failed.
A phase failure in the motor feeder cable
was detected.
The signal can also be output in the
following case:
The motor is correctly connected, how-
ever the closed-speed control is instable
and therefore an oscillating torque is
generated.
Power unit has detected a ground fault.
Ground fault in the power cables.
Winding fault or ground fault at the
motor.
12.2 List of faults and alarms
Remedy
Check the line supply voltage
Check the line supply infeed and observe
the fault messages relating to it (if there
are any)
Check the line supply phases.
Check the line supply voltage setting.
Check whether the fan is running.
Check the fan elements.
Check whether the surrounding tempera-
ture is in the permissible range.
Check the motor load.
Reduce the pulse frequency if this is high-
er than the rated pulse frequency.
Reduce the continuous load.
Adapt the load duty cycle.
Check the motor and power unit rated
currents.
Check the main circuit fuses.
Check whether a single-phase load is
distorting the line voltages.
Check the motor feeder cables.
Check the motor feeder cables.
Check the speed controller settings.
Check the power cable connections.
Check the motor.
Diagnostics