Setting MDI setpoints
When telegrams 9, 110, and 111 are used, set MDI setpoints with the following PROFINET
control words:
● Position setpoint (MDI_TARPOS): 1 hex = 1 LU
● Velocity setpoint (MDI_VELOCITY): 1 hex = 1000 LU/min
● Acceleration override (MDI_ACC): 4000 hex = 100%
● Deceleration override (MDI_DEC): 4000 hex = 100%
When telegram 7 is used, set MDI setpoints with the following parameters:
● Position setpoint (p2690)
● Velocity setpoint (p2691)
● Acceleration override (p2692)
● Deceleration override (p2693)
Intermediate stop and reject an MDI task
When telegrams 7, 9, 110, and 111 are used, reject an MDI task with the PROFINET control
word STW1.4:
Control word
When telegrams 7, 9, 110, and 111 are used, perform an intermediate stop with the
PROFINET control word STW1.5:
Control word
Overview of important parameters
• p2690
• p2691
• p2692
• p2693
For more information about the parameters above, see Section "Parameter list (Page 264)".
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2020, A5E37208830-008
Setting
STW1.4
1
0
Setting
STW1.5
1
0
MDI position, fixed setpoint
MDI velocity, fixed setpoint
MDI acceleration override, fixed setpoint
MDI deceleration override, fixed setpoint
Description
Do not reject a traversing task.
Reject a traversing task (ramp-down with the maximum
deceleration).
Description
No intermediate stop.
Intermediate stop with parameterized deceleration MDI_DEC
(telegrams 9, 110, and 111) or p2693 (telegram 7).
Control functions
7.2 Basic positioner (EPOS)
197