X26, Engineering Interface - Bosch Rexroth IndraDrive CSB02 Project Planning Manual

Control sections
Table of Contents

Advertisement

52/143
Bosch Rexroth AG
On-board connection points
6.5

X26, Engineering interface

Description
View
Properties
Standard
Compatibility
Recommended cable type
IndraDrive Control Sections CSB02, CSE02, CSH02, CDB02
Only available at CSH02.xB-CC ADVANCED devices.
Connection
Signal name
1
TD+
2
TD-
3
RD+
4
n. c.
5
n. c.
6
RD-
7
n. c.
8
n. c.
Housing
Ethernet
Type: RJ-45, 8-pin
100Base-TX according to IEEE 802.3u
According to CAT5e; type of shield ITP (Industrial Twisted Pair)
Ready-made cables which can be ordered:
RKB0011
Long cables (100 m at maximum) to connect the drive system to the high‐
er-level control unit or remote communication nodes.
Minimum bending radius:
48.75 mm if laid flexibly
32.50 mm if laid permanently
Order code for a 30 m long cable: RKB0011/030,0
RKB0013
Short cables to connect devices arranged side by side in the control cabi‐
net.
4 lengths available: 0.19 m; 0.25 m; 0.35 m; 0.55 m
Order code for a 0.55 m long cable: RKB0013/00,55
Minimum bending radius: 30.75 mm
Tab. 6-7:
Function, Pin Assignment, Properties
DOK-INDRV*-CXX02******-PR03-EN-P
Function
Transmit, differential output A
Transmit, differential output B
Receive, differential input A
-
-
Receive, differential input B
-
-
Shield connection

Advertisement

Table of Contents
loading

Table of Contents