DOK-INDRV*-CXX02******-PR03-EN-P
IndraDrive Control Sections CSB02, CSE02, CSH02, CDB02
9.2
Connection points
9.2.1
General information
9.2.2
Connection points with spring terminals
9.2.3
Connection points with screw terminal blocks
The connection points at control sections are equipped with spring terminals
and screw terminal blocks.
To connect 2 conductors in one terminal connecting point:
●
Use stranded wires with min. 0.5 mm
●
Use wires of the same cross section
●
Use TWIN ferrules
Spring terminals can be wired with wire ends equipped with or without fer‐
rules. Preferably use wire ends without ferrules.
When assembling the connections, make sure
●
that the stripped length of the wire ends is 10 mm
●
that all strands of a stranded wire are placed in the funnel of the terminal
connector
●
not to use solid wires, where possible
●
to use appropriate crimping tools for the wire ends with ferrules
On screw terminal blocks, use wire ends with ferrules. Make sure to use ap‐
propriate crimping tools.
When assembling the connections, make sure that all strands of a stranded
wire are placed in the funnel of the terminal connector.
Bosch Rexroth AG
129/143
Technical data - other
and max. 1.0 mm
2
2