Table 4-74 Storage Allocation Prompts - Honeywell VPR100 User Manual

Table of Contents

Advertisement

Storage Allocation
Choose STORAGE ALLOCATION under SET UP NEW SCHEDULES menu to see the disk capacity and
to allocate storage of each data type. See Table 4-74.
Prompt
DISK CAPACITY
TREND#1 LO RATE
Seconds: .25, .5, 1, 2, 3, 4, 5,
6, 7, 8, 9, 10, 20, 30, 40, 50
Minutes: 1, 2, 3, 4, 5, 10, 20,
30, 40, 50
Hours: 1
TREND#1 HI RATE
Seconds: .25, .5, 1, 2, 3, 4, 5,
6, 7, 8, 9, 10, 20, 30, 40, 50
Minutes: 1, 2, 3, 4, 5, 10, 20,
30, 40, 50
Hours: 1
TREND#2 LO RATE
See TREND#1 LO RATE
TREND#2 HI RATE
See TREND#1 HI RATE
TREND#3 LO RATE
See TREND#1 LO RATE
TREND#3 HI RATE
See TREND#1 HI RATE
UNIT DATA
0-10000
SAMPLES
ALARM SAMPLES
0-1600
EVENT SAMPLES
0-1600
DIAG SAMPLES
0-1600
ATTENTION
Alarm, Events, Diagnostics and Unit Data storage mode is defaulted to OFF. Each storage mode must be
enabled for storage.
12/00

Table 4-74 Storage Allocation Prompts

Range/Selections
VPR & VRX – User Manual
Programming Function Blocks and Features
Definition
Displays total time available for non-rollover trend storage
based on the low storage rates programmed. See Table
4-75 and Table 4-76. . The disk capacity will display zeros if
the storage mode is set to OFF for all 3 trends.
This rate can be altered here or in the trend data setup (see
Table 4-71). If the low storage rates are changed, the disk
capacity will reflect the new trend capacity. Enter data
collection rate. This is how often the data points are
sampled. The .25 ms selection is only available for 2-input
instruments with no more than 3 points total in Trends 1-3.
The .5 sec rate cannot exceed 6 points total in Trends 1-3.
This rate can be altered here or in the trend data setup (see
Table 4-71). If the hi storage rates are changed, the disk
capacity will reflect the new trend capacity. Enter data
collection rate. This is how often the data points are
sampled. The .25 ms selection is only available for 2-input
instruments with no more than 3 points total in Trends 1-3.
The .5 sec rate cannot exceed 6 points total in Trends 1-3.
Select maximum number of samples of unit data to be
stored. Default capacity is 1000. Shown only if unit data
was set up as part of the schedule.
Select maximum number of samples of alarm transitions
(off-to-on and on-to-off) to be stored. Default capacity is
100. Shown only if alarms were set up as part of the
schedule.
Select maximum number of samples of events to be stored.
Default capacity is 100. Shown only if events were set up
as part of the schedule.
Select maximum number of samples of diagnostics to be
stored. Default capacity is 100. Shown only if diagnostics
were set up as part of the schedule.
177