Table 1-2 Analog Input Accuracy--Linear Types - Honeywell VPR100 User Manual

Table of Contents

Advertisement

Introduction
Primary Displays
Support Displays
Communications
(optional)
SDA
SCF
Input Range
-25 to 25 mV
-75 to 75 mV
-200 to 1000 mV
-200 to 5000 mV
0 to 10 V
-10 to 10 V
0 to 20 V
-20 to 20 V
10
Table 1-1 Specifications (continued)
Performance/Capacities (continued)
Up to 10 displays may be assigned from the following formats: Vertical Trend, Vertical
Trend Digital, Horizontal Trend, Horizontal Trend Digital, Horizontal Trend Bar, 3pt Vertical
Bar Graph, 6pt. Vertical Bar Graph, Panel Display, Unit Data, Panel Meter, Alarm
Summary, Storage Status, Totalizer, Loop w/Bar Graph, Loop w/2 Bar Graphs, Loop w/3
Bar Graphs, Loop w/4 Bar Graphs, Setpoint Profiler w/2 Bar Graphs, Setpoint Profiler w/3
Bar Graphs, Setpoint Profiler Trend.
The VRX150 has these additional formats:
Panel Display w/4 Large Fonts (instead of Panel Display), Setpoint Profiler w/4 Bar
Graphs, Vertical Trend Digital, 4 pt. Vertical Bar Graph (instead of 3 pt.), Vertical Trend
Bar, 4 pt. Horizontal Bar Graph (instead of 3 pt.), 6 pt. Horizontal Bar Graph, Process
Summary
13 (menu access).
Type: RS-422/485, Honeywell Binary Modbus RTU protocol
Connection: 2 twisted pairs with shield (5 wires).
Distance: 600 meters, (2000 feet).
Number of links: Up to 30
Baud Rate: 1200, 2400, 4800, 9600, 19.2K, 38.4K, 76.8K.
Parity: Selectable; odd, even, none.
Optional Software Accessories
Data Analysis Software
Configuration Software

Table 1-2 Analog Input Accuracy--Linear types

Accuracy at Calibration Temperature
+/- Accuracy
% Range
0.02
0.02
0.02
0.03
0.5
0.5
0.5
0.5
VPR & VRX – User Manual
+/- Temperature Effects
mV
0.003 mV per °C
0.01
0.009 mV per °C
0.03
0.037 mV per °C
0.24
0.150 mV per °C
1.56
1.86 mV per °C
50
0.045 mV per °C
100
1.86 mV per °C
100
0.255 mV per °C
200
12/00