Programming Function Blocks and Features
CEMS Block Average
Outputs a block mean average CVn OV over the specified Average Period. The average is calculated from
input samples taken at equally spaced Sample Periods. All samples are discarded at the end of the Average
Period and the Average Period begins again.
Samples are ignored when Calibrate Hold is ON(1). After the Average Period the new average is calculated
using only the samples taken before and after the Hold. If no valid samples are taken, the output maintains
its previous value.
Table 4-48 describes the CEMS Block Average prompts. See Table 4-2 for additional prompts.
Prompt
RANGE LOW
RANGE HIGH
INPUT
RESET
TIME UNITS
AVERAGE PERIOD
SAMPLE PERIOD
CALIBRATE HOLD
142

Table 4-48 CEMS Block Average Prompts

Range/Selections
OFF or number
OFF, analog parameter,
number
OFF, discrete parameter, 0,
1
SECONDS, MINUTES,
HOURS, or DAYS.
OFF or number
OFF or number
OFF, discrete parameter, 0,
1
VPR & VRX – User Manual
Definition
Enter the output's display limits. Output is not clamped
or flashed when it exceeds these limits.
Input to be averaged
When discrete is ON(1), average is reset to zero; when
ON(1)-to-OFF(0), average restarts.
Time units of the averaging period
Number of time units per average period.
Number of time units between samples. Must divide
evenly into Average Period.
When ON(1), no samples are taken and the output is
held.