Setpoint Profiler
Table 5-2 Parameters That Control Profiler Execution (continued)
Parameter name
Definition
HOLD
Holds a profiler at its current position.
Profiler's Elapsed Time continues but
Segment Time stops until Profiler is started
again.
Hold is activated by online operator menu or
by a discrete input's level ON or rising edge.
To hold profile by pressing HOLD/F2 key:
1.
Set HOLD to SY1F2.
2.
Set HOLD LEVEL/EDGE to EDGE.
To hold or start multiple profiles
simultaneously, see "Holding multiple profilers
simultaneously".
HOLD
Holds a profiler at its current position.
Profiler's Elapsed Time continues but
Segment Time stops until Profiler is started
again.
Hold is activated by online operator menu or
by a discrete input. May be connected to
HOLD/F2 key (SY1F2).
ADVANCE
Advances a profiler on Hold to the starting
value of the next segment. If the profile is on
the last segment, it advances to the ending
value of the last segment. If the profile is on
the ending value of the last segment of the
batch, then it advances around to the starting
value of segment 1, or to the first segment of
the batch phase as defined by BATCH
SEGMENT FIRST. If within a loop, advances
to next segment in the loop.
Advance is activated by online operator menu
or by a discrete input.
HOT START
When HOT START is ON and the profiler is
started, the profiler begins to run at the point
in the profile where the current value of PV #1
first occurs. Hot Start makes the profiler skip
over unneeded segments.
Hot Start is activated by a discrete input.
Example
If PV #1 is 100 and the profile contains the
value 100 in Segment 4 and Segment 6, HOT
START forces the profiler to start running at
Segment 4 at 100, not at Segment 1 or
Segment 6.
See Figure 5-11.
196
Triggered
by
Level ON
or Rising
Edge
(depends
on setting
of profile's
HOLD
LEVEL/
EDGE
prompt)
Level ON
Rising
edge
Level ON
VPR & VRX – User Manual
Conditions
Result
present
Profiler is in
Profiler is
Run or Hold
put in Hold.
Profiler is in
Profiler is
Run or Hold
put in Hold.
Profiler is in
Profiler
Hold
advances.
Profiler is in
When
Ready.
profiler
changes
from Ready
to Run,
profiler
jumps to
the same
value as
PV #1.