Honeywell VPR100 User Manual page 295

Table of Contents

Advertisement

Error
Invalid Tag Request
Invalid Type in Point
Spec
Lag or Delay Less than
Zero
Low Limit Outside of
Circuit
Low limit Outside of
Table
Low Output Limit less
than Zero
Monthly Periods Must Be
Phased
No Room for Function
Block
Number of Frames Out
of Range
Out of EEPROM Memory
Out of RAM Memory
Output Limits Equal
Pairs Inconsistent
Request Made with
Invalid Tag
Requires a Deviation
Parameter
Requires Input
Parameter
Requires Setpoint
Parameter
RJ Not in Curve
12/00
Table 10-1 Error Messages (continued)
Description
Probably caused by someone incorrectly editing
the configuration file or by a corrupt .LNC file.
A class of block was detected that is invalid for
the product.
AI lag or delay is less than zero
AI circuit low limit is < voltage limit of -500 mV.
For thermocouple or RTD, Range Low limit is <
the low limit for that type.
A current output (CAT) or voltage output (VAT)
low limit is less than zero.
Periodic Timer CV period is monthly but no
phase is defined
System has used all allocated function blocks.
Rolling Average CV # of Samples is less than 1
or greater than 60.
No more static memory or EEPROM memory
No more RAM available
Output (range) limits (low and high) must be
unequal.
Applies to custom AI or Function Generator CV.
Curve has Xn but no Yn or vice versa. Curve
does not have at least 2 X,Y pairs.
Probably caused by someone incorrectly editing
the configuration file or by a corrupt .LNC file.
Deviation alarm does not contain deviation.
Alarm does not contain an input.
Alarm does not contain a setpoint.
AI is custom type, class thermocouple, RJ
enabled but curve does not contain 0-65
degrees C (32-149 degrees F).
VPR & VRX – User Manual
Error Messages
User Action
Verify programming of affected
function block.
Verify programming of affected
function block.
Change lag or delay to greater than
or equal to zero.
Change circuit low limit to > -500 mV.
Change limit to within specified limits
for that type. (Table 4-6)
Change current output (CAT) or
voltage output (VAT) low limit to
greater than or equal to zero.
Change Periodic Timer phase.
Verify programming of affected
function block.
Change # of Samples to 1-60.
Verify programming of affected
function block.
Verify programming of affected
function block.
Change to unequal limits
Program a Y for each X or vice versa.
Program at least 2 X's and 2 Y's.
Verify programming of affected
function block.
Program alarm with deviation.
Program alarm with input.
Program alarm with a setpoint.
Y values must contain 0-65 degrees
C (32-149 degrees F).
279