Figure 3-26 Function Block Diagram Of The Cascade Control Strategy - Honeywell VPR100 User Manual

Table of Contents

Advertisement

Programming and Operating Concepts
REACTION
VESSEL
THERMOCOUPLE
OIL
THERMOCOUPLE

Figure 3-26 Function Block Diagram Of The Cascade Control Strategy

Recall that based on the instrument's model number, up to four control loops (LP1 through LP4) are
potentially available for use within the instrument. All control loops in this product may be programmed to
operate using up to two user defined set point parameters, designated by SP1 and SP2. Should you
implement a control loop using one or both setpoints? That depends on what is necessary to meet the
requirements of the specific application being dealt with. When in the on line mode and viewing a control
loop's dedicated on line display, the working set point of the live control loop can be switched between SP1
or SP2 by simply pushing the "SP" key on the instrument's front bezel. Note that while both set point
parameters may be programmed to have straight numeric values, only SP2 may be defined as a remote set
point. That is, SP2 may be set up so that its value is determined by the output value of another function
block, such as a setpoint profile. In the cascade control strategy demonstrated in Figure 3-26, SP2's remote
set point functionality is exploited by the LP2 secondary cascade loop. When this control configuration is
made operational, LP2's working set point, SP2, will have a value determined by LP1 OV.
In Figure 3-26, the process values of each loop are the output values of the AI1 and AI2 analog input
function blocks. AI1 will produce temperature measurements of the reaction chamber and provide them to
the process variable input of LP1, while measurements of the oil temperature in the jacket tank will be
furnished to LP2's PV input by AI2. Because LP1 OV will provide LP2 with its operating set point, LP1's
output range will be defined in engineering units of temperature instead of the usual 0 to 100 %. LP2's
output range is 0 to 100%, in anticipation of using it to drive the AO1 function block's 4 to 20 mA signal.
Note that the range covered by LP1 OV will have to be consistent with the operating temperature range of
the oil. For example, if it is determined that the oil temperature will be manipulated between 75 and 500 ºF,
the low and high limits assumed by LP1 OV (and, for that matter, SP2) will equal 75 and 500, respectively.
Finally, LP2 BC and AO1 BC are the two back-calculated feedback paths shown. As is true for the
operation of all back-calculated feedback paths, both LP2 BC and AO1 BC work together to acknowledge
the cascaded control loops that the appropriate actions have taken place in response to both loops' output
values.
The method used to coordinate the tuning of the cascaded loops is particularly interesting. Using the
diagram of Figure 3-26, the first priority is to tune the secondary cascade loop of LP2. With LP1 kept in
manual mode, tuning may begin by first placing LP2 in manual mode and then manipulating LP1's output.
This will allow the generation an LP2 set point that will induce a process upset when the secondary loop is
placed back in automatic mode. Only after LP2 has been tuned can LP1 be tuned. When tuning LP1, LP2
will be kept in automatic mode throughout the entire time LP1 is exercised. Since the tuning of LP2 will
have already been established, tuning LP1 may be approached by first mentally "blocking out" the
secondary control loop's existence and visualizing LP1's output as connected to a sort of virtual analog
68
AI1 OV
FB
AI1
PV
TYPE = CAS_P
SP1 = 1234.5
AI2 OV
AI2
NOTE:
1) SP1 is desired reaction vessel temperature.
2) SP2 is the remote setpoint input of LP2.
VPR & VRX – User Manual
LP2 BC
AO1 BC
LP1 OV
FB
LP1
SP2
LP2
PV
TYPE = CAS_S
LP2 OV
4 TO 20 mA
IN
AO1
12/00

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrx100Vrx150

Table of Contents