Table 4-27 Free Form Logic Prompts; Figure 4-7 Free Form Logic Signal Flow - Honeywell VPR100 User Manual

Table of Contents

Advertisement

Free Form Logic
Lets you enter up to 64 characters as a custom logic equation (EQ) containing inputs and logical operators.
The result of this equation is called "Result". Result is then processed according to the specified condition
type and condition time. The final output is CVn OS. See Figure 4-7 .
Table 4-27 describes the Free Form Logic prompts. See Table 4-2 for additional prompts.
Prompt
EQ
*
+
^
NEG
A, B, C, D, E, F, G, H
O
1
0
( )
INPUT A - INPUT H
OFF, discrete parameter, 0,
1.
RESET
OFF, discrete parameter, 0,
1
CONDITION TYPE
NONE, DELAY, EXTEND,
PULSE, RT PULSE
CONDITION TIME
OFF or number
12/00
Inputs
A
B
C
FREE FORM
D
LOGIC
E
EQUATION
F
G
H

Figure 4-7 Free Form Logic Signal Flow

Table 4-27 Free Form Logic Prompts

Range/Selections
VPR & VRX – User Manual
Programming Function Blocks and Features
CONDITION
TYPE
Result
&
CONDITION
TIME
Definition
Symbol for AND operator
Symbol for OR operator
Symbol for XOR operator
Symbol for NOT operator
Symbols for Input A through Input H
Letter O is the symbol for output CVn OS from the previous
logic calculation. Use for iterative calculations.
One = ON
Zero = OFF
Expressions enclosed by parentheses are evaluated first.
Up to 8 input sources.
Resets the output to OFF (0). Use when using the letter O
in equations.
See Table 4-20 on page 111.
Enter number of seconds of condition time. See Table
4-20 on page 111.
CVn OS
119

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrx100Vrx150

Table of Contents