Online Operation Using Menus

7.5 Data Entry

Data Entry lets you enter or revise data online. Choices available depend on installed options and enabled
features (see "Enable Features" in Section 4.19).
Edit Alarm Setpoints
Select this item to display a list of alarms and their setpoints. If the setpoint is a numeric value, it can be
changed on this display using the Up Arrow and Down Arrow buttons. If it is programmed as a parameter,
it cannot be changed here.
Edit Constants
Select this item to display or change a list of all constants in the instrument. To change a value, use the Up
Arrow and Down Arrow buttons.
Force Discrete Inputs/Outputs
Select either of these items to display or force the status of any discrete.
The STATE indicates ON or OFF. FORCE/RELEASE indicates if the discrete is forced or released
(unforced). To force a discrete, select FORCE ON or FORCE OFF. To release a forced discrete, select
RELEASE. Adjust with Up Arrow and Down Arrow. Press Enter to enter the changes. Press Menu to
leave the menu.
Adjust Analog Inputs
Select this item to display a list of all the analog inputs presently configured. Analog Input Adjust may be
applied or removed from any AI on the list. If the AI point has been configured with a pyrometer range, the
Input Adjust is applied as a multiplier (equal to the newly entered value divided by the actual measured
valued at the time that the adjustment is entered). In this case, the Value Adjust is referred to as an
"emissivity" adjustment. If the AI point has been configured with any other range, the value adjust is
applied as a bias (equal to the newly entered value minus the actual measured value at the time that the
adjustment is entered).
All points on the display which are currently adjusted will have a Value Adjust Indicator (*) beside the
value.
To adjust a value, select the desired AI and press Enter. Use the Up Arrow, Down Arrow and Enter buttons
to change the value on the display. The value can be changed to any value within the programmed limits of
the AI.
To remove the value adjustment, set the value to OFF. The AI will display its current value and the
indicator (*) will be removed.