Table 4-20 Compare's Condition Type And Condition Time Prompts - Honeywell VPR100 User Manual

Table of Contents

Advertisement

Condition type
NONE
Condition type
DELAY
If Result is:
Then CVn OS is:
Condition type
EXTEND
If Result is:
Then CVn OS is:
12/00

Table 4-20 Compare's Condition Type and Condition Time Prompts

Application
--
Application
Filters short pulses
Delays rising edge of Result for
CONDITION TIME
1 sec
Not on at least 3 sec
Time
Application
Used for interfacing with slower
circuits.
Extends falling edge of Result
for CONDITION TIME.
1 sec
3 sec extend
Time
VPR & VRX – User Manual
Programming Function Blocks and Features
If this is true
Result
If this is true
Result switches ON(1) for n
seconds ≥ CONDITION TIME.
Result switches OFF(0)
Condition Type = Delay
Condition Time = 3 seconds
2 sec
3 sec delay
If this is true
Result switches ON(1) for n
seconds, then OFF(0)
Result switches ON(1)
Condition Type = Extend
Condition Time = 3 seconds
2 sec
then CVn OS is
Result
then CVn OS is
ON n seconds minus
CONDITION TIME
OFF(0)
On at least 3 sec
2 sec
then CVn OS is
ON(1) for n seconds plus
CONDITION TIME, then
OFF(0)
ON with no delay
3 sec extend
111