Honeywell VPR100 User Manual page 294

Table of Contents

Advertisement

Error Messages
Error
Incorrect Input
coordinates
Incorrect Number of
Parameters for function
Incorrect Output
Coordinates
Invalid Algorithm Code
Invalid Block Number
Invalid Block Type
Invalid Channel in Point
spec
Invalid Equation
Invalid Function Block
Request
Invalid Index code
Invalid Input Connection
Invalid Machine Update
Rate
Invalid Parameter Code
Invalid Parameter for
Data Type
Invalid Tag
278
Table 10-1 Error Messages (continued)
Description
The Advanced Splitter CV was programmed
with input limits for Output#2 (A2) only, or for
Output#1 & #3 (A1 & A3) only, or for Output#3
(A3) only.
The function was not programmed with the
minimum number of parameters. for example,
the Math CV requires at least 2 inputs to
function properly.
The Advanced Splitter CV was programmed
with output limits for Output#2 (A2) only, or for
Output#1 & #3 (A1 & A3) only, or for Output#3
(A3) only.
Bad algorithm code has been given, bad
algorithm choice. Probably caused by
someone incorrectly editing the configuration
file or by a corrupt .LNC file.
Probably caused by someone incorrectly editing
the configuration file or by a corrupt .LNC file.
Probably caused by someone incorrectly editing
the configuration file or by a corrupt .LNC file.
Invalid channel has been found
Free form math equation is invalid.
Probably caused by someone incorrectly editing
the configuration file or by a corrupt .LNC file.
Probably caused by someone incorrectly editing
the configuration file or by a corrupt .LNC file.
Function block is programmed with wrong input
type. Probably caused by someone incorrectly
editing the configuration file or by a corrupt
.LNC file.
Bad machine scan rate
Bad parameter code has been found.
Generally caused by transferring configurations
between instruments with different software
versions.
Probably caused by someone incorrectly editing
the configuration file or by a corrupt .LNC file.
Probably caused by someone incorrectly editing
the configuration file or by a corrupt .LNC file.
VPR & VRX – User Manual
User Action
Re-program input limits for Output#1
only, Outputs #1 & #2, or Outputs #1,
#2, & #3.
Program function with at least the
minimum number of parameters.
Re-program output limits for
Output#1 only, Outputs #1 & #2, or
Outputs #1, #2, & #3.
Verify programming of affected
function block.
Verify programming of affected
function block.
Verify programming of affected
function block.
Verify programming of affected
function block.
Check equation.
Verify programming of affected
function block.
Verify programming of affected
function block.
Verify programming of affected
function block.
Re-enter machine scan rate.
Verify programming of affected
function block.
Verify programming of affected
function block.
Verify programming of affected
function block.
12/00