Setpoint Profiler

5.3 Parameters that control a profile's execution

Coordinating operation of multiple profilers
In a multi-profiler instrument the profiles in a program can be totally unrelated to each other, that is, you
can give them different times and settings. If you want the profilers to be coordinated, you must configure
each profiler that way. For example, if you want all your profilers to be started by the same signal, you
must configure each profiler with the same START parameter. The Copy Block function in the Program
menu lets you copy parameters from one profiler to another.
Holding multiple profilers simultaneously
The figure below shows how to configure your instrument to hold all profilers when one or more profilers
enters the Hold state because of a guaranteed soak. Also shown is how to configure it to hold or start all
profilers by pressing the F2/HOLD key. Note that any profiler can still be put in Hold through the popup
profile menu (Table 5-14, page 214 ); doing so will not Hold the other profilers.
194
Calc.
CVx OS
Value
Logic
OR
Calc. Value Logic
TOGGLE/FF
SY1 F2
INPUT A

Figure 5-10 Holding multiple profilers simulaneously

VPR & VRX – User Manual
HOLD
Profiler#1
SP1 SG
Profiler#2
HOLD
SP2 SG
HOLD
Profiler#3
SP3 SG
SP4 SG
HOLD
Profiler#4
To hold or start all profiles by
pressing F2/Hold key,
program a Logic TOGGLE/FF
CVy OS
CV as shown and input it to
the Logic OR CV.
Set all
Profilers HOLD
LEVEL/EDGE
to LEVEL.