1 Point Block Average (1 Pt Block Avg)
Outputs a block mean average CVn OV of the input over the specified Average Period. A new sample of
the input will be taken on every instrument scan cycle. The block average is only updated at the end of the
Average Period.
When the Reset Input is ON(1) all accumulated samples are discarded and the output is held until the Reset
Input is OFF(0), then the averaging period resets.
Table 4-45 describes the 1 Point Block Average prompts. See Table 4-2 for additional prompts.
Prompt
RANGE LOW
OFF or number
RANGE HIGH
INPUT
OFF, analog parameter,
number
RESET
OFF, discrete parameter, 0, 1
AVERAGE PERIOD
0.1 to 1440
12/00

Table 4-45 1 Point Block Average Prompts

Range/Selections
VPR & VRX – User Manual
Programming Function Blocks and Features
Definition
Enter the output's display limits. Output is not clamped or
flashed when it exceeds these limits.
This parameter will be averaged
When the Reset is ON(1) all accumulated samples are
discarded and the output is held until the Reset is OFF(0),
then the averaging period resets.
Length of averaging period in minutes